Data Sheet

Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm
-1
at 50 Hz or 1800 min
-1
at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 400 V, 50 Hz
150 % Overload P kW 0.75
Note at 440 - 480 V, 60 Hz
150 % Overload P HP 1
Apparent power
Apparent power at rated operation 400 V S kVA 1.45
Apparent power at rated operation 480 V S kVA 1.75
Braking function
Standard braking torque max. 30 % M
N
DC braking torque adjustable to 100 %
Control section
Reference voltage U
s
V 10 V DC (max. 0.2 mA)
Analog inputs 1, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Digital inputs 4, parameterizable, 10 - 30 V DC
Relay outputs 1, N/O contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU
Assigned switching and protective elements
Power Wiring
Safety device (fuse or miniature circuit-breaker)
IEC (Type B, gG), 150 % FAZ-B6/3
UL (Class CC or J) A 6
Mains contactor
150 % overload (CT/I
H
, at 50 °C) DILM7-…
Main choke
150 % overload (CT/I
H
, at 50 °C) DX-LN3-004
Radio interference suppression filter (external, 150 %) DX-EMC34-008
Radio interference suppression filter, low leakage currents (external, 150 %) DX-EMC34-008-L
Note regarding radio interference suppression filter Optional external radio interference suppression filter for longer motor cable
lengths and for use in different EMC environments
Motor feeder
motor choke
150 % overload (CT/I
H
, at 50 °C) DX-LM3-008
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 2.1
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 28
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -10
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
06/18/2021 Eaton 174334 ED2021 V80.0 EN 3 / 6