Data Sheet
150 % Overload P kW 2.2
Note at 220 - 240 V, 60 Hz
150 % Overload P HP 3
Apparent power
Apparent power at rated operation 230 V S kVA 3.82
Apparent power at rated operation 240 V S kVA 3.99
Braking function
Standard braking torque max. 30 % M
N
DC braking torque adjustable to 100 %
Control section
Reference voltage U
s
V 10 V DC (max. 0.2 mA)
Analog inputs 1, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Digital inputs 4, parameterizable, 10 - 30 V DC
Relay outputs 1, N/O contact, 6 A (250 V, AC-1) / 5 A (30 V, DC-1)
Interface/field bus (built-in) OP-Bus (RS485)/Modbus RTU
Assigned switching and protective elements
Power Wiring
Safety device (fuse or miniature circuit-breaker)
IEC (Type B, gG), 150 % FAZ-B32/1N
UL (Class CC or J) A 35
Mains contactor
150 % overload (CT/I
H
, at 50 °C) DILM7-… + DILM12-XP1
Main choke
150 % overload (CT/I
H
, at 50 °C) DX-LN1-024
Radio interference suppression filter (external, 150 %) DX-EMC12-025-FS2
Note regarding radio interference suppression filter Optional external radio interference suppression filter for longer motor cable
lengths and for use in different EMC environments
Motor feeder
motor choke
150 % overload (CT/I
H
, at 50 °C) DX-LM3-011
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 9.6
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 105
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -10
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
06/18/2021 Eaton 174332 ED2021 V80.0 EN 3 / 6