Data Sheet
Radio interference class (EMC) C1 (for conducted emissions only), C2, C3, depending on the motor cable length, the
connected load, and ambient conditions. External radio interference suppression
filters (optional) may be necessary.
Environment (EMC) 1st and 2nd environments as per EN 61800-3
maximum motor cable length I m C1 ≤ 5 m
C2 ≤ 10 m
C3 ≤ 25 m
Mechanical shock resistance g 15 (11 m/s, EN 60068-2-27)
Vibration EN 61800-5-1
Altitude m 0 - 1000 m above sea level
Above 1000 m: 1% derating for every 100 m
max. 2000 m
Degree of Protection IP20/NEMA0
Protection against direct contact BGV A3 (VBG4, finger- and back-of-hand proof)
Main circuit
Supply
Rated operational voltage U
e
230 V AC, 1-phase
240 V AC, single-phase
Mains voltage (50/60Hz) U
LN
V 200 (-10%) - 240 (+10%)
Input current (150% overload) I
LN
A 23.2
Supply frequency f
LN
Hz 50/60
Frequency range f
LN
Hz 45–66 (± 0%)
Mains switch-on frequency Maximum of one time every 30 seconds
Power section
Overload current (150% overload) I
L
A 14.4
max. starting current (High Overload) I
H
% 200
Note about max. starting current for 1.875 seconds every 600 seconds
Output voltage with V
e
U
2
230 V AC, 3-phase
240 V AC, 3-phase
Output Frequency f
2
Hz 0 - 50/60 (max. 300)
Switching frequency f
PWM
kHz 16
adjustable 4 - 32 (audible)
Operation Mode U/f control
Speed control with slip compensation
Frequency resolution (setpoint value) Δf Hz 0.025
Rated operational current
At 150% overload I
e
A 9.6
Note Rated operational current at an operating frequency of 16 kHz and an ambient air
temperature of +50°C
Heat dissipation at current/speed [%]
Current = 100%
Speed = 0 % P
V
W 72
Speed = 50 % P
V
W 72
Speed = 90 % P
V
W 91
Current = 50 %
Speed = 0 % P
V
W 46
Speed = 50 % P
V
W 46
Speed = 90 % P
V
W 55
Current = 50 %
Speed = 0 % P
V
W 30
Speed = 50 % P
V
W 38
Maximum leakage current to ground (PE) without motor I
PE
mA < 3.5 AC, < 10 DC
Fitted with Radio interference suppression filter
Frame size FS2
Motor feeder
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm
-1
at 50 Hz or 1800 min
-1
at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 230 V, 50 Hz
06/18/2021 Eaton 174332 ED2021 V80.0 EN 2 / 6