Data Sheet

DATASHEET - D125-CI43
Cap, transparent smoky gray, HxWxD=250x375x25mm
Part no. D125-CI43
Catalog No. 017203
EL-Nummer
(Norway)
0002502144
Delivery program
Product range xEnergy Safety Ci
Basic function Basic enclosures
Product function Enclosure cover
Accessories Enclosure cover without apertures
Single unit/Complete unit Modular system
Standards EN 62208
EN 61439-2
Description Sealable cover fasteners
Type cover Transparent
Colour Transparent, smoky gray
Dimensions
Width mm 375
Height mm 250
Mounting depth: mm 125
For use with U-CI43…
Design verification as per IEC/EN 61439
Technical data for design verification
Heat dissipation, at an ambient temperature of 35°C, delta T: 20 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure for wall mounting P
V
W 12
Starting enclosure for wall mounting P
V
W 12
Middle enclosure for wall mounting P
V
W 12
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure for wall mounting P
V
W 24
Starting enclosure for wall mounting P
V
W 24
Middle enclosure for wall mounting P
V
W 24
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Not relevant to indoor installations.
10.2.5 Lifting 10 kg per enclosure with support frame and lifting aid met; assembled and secured
as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact IK10
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES IP65, with base unit
10.4 Clearances and creepage distances Is the panel builder's responsibility.
10.5 Protection against electric shock Protection class 2, therefore not applicable.
06/18/2021 Eaton 017203 ED2021 V80.0 EN 1 / 2