Data Sheet

DATASHEET - EU5C-SWD-PROFINET
Gateway, SWD, 99 SWD cards on PROFINET
Part no. EU5C-SWD-PROFINET
Catalog No. 170124
Alternate Catalog
No.
EU5C-SWD-PROFINET
EL-Nummer
(Norway)
4560870
Delivery program
Product range SmartWire-DT coordinators
Function for connection to field bus PROFINET as PROFINET IO-Device
Short Description Used to connect the SmartWire-DT communication system to industrial field bus
systems. Powers SmartWire-DT modules and switchgear
Description SmartWire-DT gateway for connecting up to 99 SmartWire-DT modules to an
Industrial Ethernet network and for powering the SmartWire-DT modules and
switchgear.
A connection to PROFINET as a PROFINET I/O device can be established using the
integrated 100 Mbit/s Ethernet switch and a slave configuration.
The gateway features a separate USB diagnostic interface (mini USB).
Accessories Connection of up to 99 SWD slaves
Technical data
General
Standards IEC/EN 61131-2
Approvals
Approvals UL
CSA
Dimensions (W x H x D) mm 35 x 90 x 124
Weight kg 0.16
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Mounting position As required
Ambient conditions, mechanical
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 61131-2:2008)
Constant amplitude 3,5 mm Hz 5 - 9
Constant acceleration 1 g Hz 9 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms Impacts 9
Drop to IEC/EN 60068-2-31 Drop height mm 50
Free fall, packaged (IEC/EN 60068-2-32) m 1
Electromagnetic compatibility (EMC)
Overvoltage category II
Pollution degree 2
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3) kV 8
Contact discharge (Level 2) kV 4
Electromagnetic fields (IEC/EN 61131-2:2008)
80 - 1000 MHz V/m 10
1.4 - 2 GHz V/m 3
2 - 2.7 GHz V/m 1
Radio interference suppression EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
Supply cable kV 2
Fieldbus cable kV 1
SmartWire-DT cable kV 1
Surge (IEC/EN 61131-2:2008, Level 1)
Supply cable 0.5kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) V 10
06/16/2021 Eaton 170124 ED2021 V80.0 EN 1 / 5

Summary of content (5 pages)