Data Sheet

Speed = 50 % P
V
W 194
Speed = 90 % P
V
W 216
Current = 50 %
Speed = 0 % P
V
W 136
Speed = 50 % P
V
W 165
Maximum leakage current to ground (PE) without motor I
PE
mA 2.47
Fitted with Radio interference suppression filter
Brake chopper
Additional PCB protection
OLED display
Safety function STO (Safe Torque Off, SIL2, PLd Cat 3)
Frame size FS4
Motor feeder
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm
-1
at 50 Hz or 1800 min
-1
at 60 Hz
Note Overload cycle for 60 s every 600 s
Note at 400 V, 50 Hz
150 % Overload P kW 15
Note at 440 - 480 V, 60 Hz
150 % Overload P HP 20
maximum permissible cable length I m screened: 100
screened, with motor choke: 200
unscreened: 150
unscreened, with motor choke: 300
Apparent power
Apparent power at rated operation 400 V S kVA 20.78
Apparent power at rated operation 480 V S kVA 24.94
Braking function
Standard braking torque max. 30 % M
N
DC braking torque max. 100% of rated operational current I
e,
variable
Braking torque with external braking resistance Max. 100% of rated operational current I
e
with external braking resistor
minimum external braking resistance R
min
22
Switch-on threshold for the braking transistor U
DC
V 780 V DC
Control section
External control voltage U
c
V 24 V DC (max. 100 mA)
Reference voltage U
s
V 10 V DC (max. 10 mA)
Analog inputs 2, parameterizable, 0 - 10 V DC, 0/4 - 20 mA
Analog outputs 2, parameterizable, 0 - 10 V, 0/4 - 20 mA
Digital inputs 3, parameterizable, max. 30 VDC, max. 5 for non-parameterized analog inputs
Digital outputs 2, parameterizable, 24 V DC
Relay outputs 2, parameterizable, 1 N/O and 1 changeover contact, 6 A (250 V, AC-1) / 5 A (30 V,
DC-1)
Interface/field bus (built-in)
OP-Bus (RS485)/Modbus RTU, CANopen
®
Assigned switching and protective elements
Power Wiring
Safety device (fuse or miniature circuit-breaker)
IEC (Type B, gG), 150 % FAZ-B50/3
UL (Class CC or J) A 50
Mains contactor
150 % overload (CT/I
H
, at 50 °C) DILM17
Main choke
150 % overload (CT/I
H
, at 50 °C) DX-LN3-040
Radio interference suppression filter (external, 150 %) DX-EMC34-042
Radio interference suppression filter, low leakage currents (external, 150 %) DX-EMC34-042-L
Note regarding radio interference suppression filter Optional external radio interference suppression filter for longer motor cable
lengths and for use in different EMC environments
DC link connection
Braking resistance
06/16/2021 Eaton 169391 ED2021 V80.0 EN 3 / 6