Data Sheet

Middle enclosure, free-standing P
V
W 22
Individual enclosure for wall mounting P
V
W 23
Starting enclosure for wall mounting P
V
W 21
Middle enclosure for wall mounting P
V
W 19
Heat dissipation, at an ambient temperature of 35°C, delta T: 35 degrees in top
of the enclosure, calculated as per IEC 60890
Individual enclosure, free-standing P
V
W 51
Starting enclosure, free-standing P
V
W 47
Middle enclosure, free-standing P
V
W 43
Individual enclosure for wall mounting P
V
W 47
Starting enclosure for wall mounting P
V
W 43
Middle enclosure for wall mounting P
V
W 39
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Lower part: 960 °C / cover: 850 °C; meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Not relevant to indoor installations.
10.2.5 Lifting 10 kg per enclosure with support frame and lifting aid met; assembled and secured
as per the latest applicable instruction leaflet.
10.2.6 Mechanical impact IK10
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES IP65
10.4 Clearances and creepage distances Is the panel builder's responsibility.
10.5 Protection against electric shock Protection class 2, therefore not applicable.
10.6 Incorporation of switching devices and components Is the panel builder's responsibility.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength U
i
= 1000 V AC
10.9.3 Impulse withstand voltage 8kV
10.9.4 Testing of enclosures made of insulating material Meets the product standard's requirements.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility.
10.12 Electromagnetic compatibility Is the panel builder's responsibility.
10.13 Mechanical function Meets the product standard's requirements.
Technical data ETIM 7.0
Distribution boards (EG000023) / Empty cabinet (EC000058)
Electric engineering, automation, process control engineering / Electrical installation, device / Electrical distribution system (incl. small distribution board) / Empty cabinet (small distribution
board) (ecl@ss10.0.1-27-14-24-08 [ACN385011])
Mounting method Surface mounted (plaster)
Type of cover Optional
Cover model Closed
Type of door None
Transparent cover/door Yes
With lock No
Nominal current (In) A 1600
Height mm 375
Width mm 250
Depth mm 225
Built-in depth mm 200
Internal depth mm 200