Data Sheet
DATASHEET - RASP-512AI1SL-C320S1
Speed controller, 5.6 A, 2.2 kW, 230/277 V AC, AS-Interface®, S-7.4 for 31
modules, with braking resistance, with fan
Part no. RASP-512AI1SL-C320S1
Catalog No. 150183
Alternate Catalog
No.
RASP-512AI1SL-C320S1
Delivery program
This item is only available until 06/30/2020, after which it will be replaced with the
following item: 198570, RASP5-5402A31-5120100S1.
Parameterization requires drivesConnect software and accessories or a key pad.
Product range Speed controller
Rated operational voltage U
e
400 V AC, 3-phase
480 V AC, 3-phase
Output voltage with V
e
U
2
0 - U
LN
Mains voltage (50/60Hz) U
LN
V 380 (-15%) - 480 (+10%)
Rated operational current
At 150% overload I
e
A 5.6
assigned motor rating P
Note at 400 V, 50 Hz
150 % Overload P kW 2.2
Note at 480 V, 60 Hz
150 % Overload P HP 3
Note for normal internally and externally ventilated 4 pole, three-phase asynchronous
motors with 1500 rpm
-1
at 50 Hz or 1800 min
-1
at 60 Hz
Description integrated PTC thermistor monitoring and Thermoclick with safe isolation
Two sensor inputs through M12 sockets (max. 150 mA) for quick stop and
interlocked manual operation
optional: 4 sensor inputs with M12-Y adapter for switchover to creep speed
Connection of supply voltage via adapter cable on round or flexible busbar junction
Diagnostics and reset on device and via AS-Interface
with AUTO - OFF/RESET - HAND key switches
3 fixed speeds and 1 potentiometer speed
can be switched over from U/f to (vector) speed control
with selector switch REV - OFF - FWD
optional: Faster stop if external 24 V fails
Control voltage external brake (50/60 Hz) V 230/277 V AC
Interface/field bus (built-in)
AS-Interface
®
AS-Interface profile cable S-7.4 for 31 modules
Braking resistance with braking resistance
Fan with fan
Instructions for actuation of motors with mechanical brake
integrated brake chopper with braking resistance for dynamic braking
Technical data
General
Standards IEC/EN 61800-5-1
UL 61800-5-1
Guideline 2011/65/EU (RoHS)
CE approval
UL approval
Climatic proofing ρ
w
% < 95%, non-condensing
IEC/EN 50178
Ambient temperature
Operating ambient temperature min. °C 0
Operating ambient temperature max. °C + 45
Storage ϑ °C -30 - +70
Overvoltage category III
Rated impulse withstand voltage U
imp
kV 2
Radio interference level
Environment (EMC) 2. Environment, Class C3
06/18/2021 Eaton 150183 ED2021 V80.0 EN 1 / 4