Safety for firefighters
The Eaton fireman's switch is installed at or shortly after the entry of the DC
string lines into the building
. The fireman's switch opens automatically with
the aid of its built-in undervoltage release
when the firefighters isolate the
fire location from mains power through the public utility and/or at the PV Off
switch
.
Tripping of the fireman's switch isolates the DC lines between PV modules and
inverter
.
This protects emergency personnel from both direct contact with live
cables and indirect contact, for example through flooding.
Tripping is indicated through a signal lamp connected to the feedback contacts,
provided power is present
.
Simple PV fireman's switch
For smaller photovoltaic installations with one or two identical strings the
simplest version of Eaton’s proven fireman's switch is the ideal choice. With a
current carrying capacity of 30 A at 1000 V DC this device is capable of reliably
switching all popular module models.
And if the inverter does not contain a built-in switch-disconnector,
the SOL30-SAFETY can fulfil this task according to VDE 0100-712.
Multi-way fireman's switch
If a photovoltaic installation consists of several strings – which is the case in all
larger systems – the new versions of the fireman’s switch with 2, 3, 4 or 6
inputs are the most efficient solution. Each string is routed through its own
switch-disconnector and then on to the inverter. This is particularly interesting
for plants whose strings have different characteristics or are exposed to differ-
ing shade ratios. Smaller inverters with several MPP trackers are often used
here.