Data Sheet

AC operated Pick-up 0.7 x U
S min
- 1.15 x U
S max
DC operated Pick-up 0.7 x U
S min
- 1.15 x U
S max
AC operated Drop-out 0.2 x U
S max
- 0.6 x U
S min
DC operated Drop-out 0.2 x U
S max
- 0.6 x U
S min
Power consumption of the coil in a cold state and 1.0 x U
S
Note on power consumption Control transformer with u
k
≦ 6%
Pull-in power Pick-up VA 380
Pull-in power Pick-up W 250
Sealing power Sealing VA 10.5
Sealing power Sealing W 5.5
Duty factor % DF 100
Changeover time at 100 % U
S
(recommended value)
Main contacts
Closing delay ms 100
Opening delay ms 110
Behaviour in marginal and transitional conditions
Sealing
Voltage interruptions
(0 … 0.2 x U
c min
) ≦ 10 ms Time is bridged successfully
(0 … 0.2 x U
c min
) > 10 ms Drop-out of the contactor
Voltage drops
(0.2 … 0.6 x U
c min
) ≦ 12 ms Time is bridged successfully
(0.2 … 0.6 x U
c min
) > 12 ms Drop-out of the contactor
(0.6 … 0.7 x U
c min
) Contactor remains switched on
Excess voltage
(1.15 … 1.3 x U
c max
) Contactor remains switched on
Pick-up phase
(0 … 0.7 x U
c min
) Contactor does not switch on
(0.7 x U
c min
… 1.15 x U
c max
) Contactor switches on with certainty
Admissible transitional contact resistance (of the external control circuit device
when actuating A11)
mΩ ≦ 500
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2)
High V 15
Low V 5
Electromagnetic compatibility (EMC)
Electromagnetic compatibility This product is designed for operation in industrial environments (environment A).
Its use in residential environments (environment B) may cause radio-frequency
interference, requiring additional noise suppression measures.
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V
208 V
HP 100
230 V
240 V
HP 125
460 V
480 V
HP 250
575 V
600 V
HP 300
General use A 350
Auxiliary contacts
Pilot Duty
AC operated A600
DC operated P300
General Use
AC V 600
06/16/2021 Eaton 139556 ED2021 V80.0 EN 5 / 12