Data Sheet

Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix
F (not N/C late open)
Instructions integrated suppressor circuit in actuating electronics
660 V, 690 V or 1000 V: not directly reversing
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operated Operations
x 10
6
10
DC operated Operations
x 10
6
10
Operating frequency, mechanical
AC operated Operations/h 3000
DC operated Operations/h 3000
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -40 - +60
Enclosed °C - 40 - + 40
Storage °C - 40 - + 80
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 10
N/C contact g 8
Degree of Protection IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof with terminal shroud or terminal block
Altitude m Max. 2000
Weight
AC operated kg 7.1
DC operated kg 7.1
Weight kg 7.1
Terminal capacity main cable
Flexible with cable lug
mm
2
50 - 240
Stranded with cable lug
mm
2
70 - 240
Solid or stranded AWG 2/0 - 500 MCM
Flat conductor Lamellenzahl
x Breite x
Dicke
mm Fixing with flat cable terminal or cable terminal blocks
See terminal capacity for cable terminal blocks
Busbar Width mm 25
Main cable connection screw/bolt M10
Tightening torque Nm 24
Terminal capacity control circuit cables
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 18 - 14
Control circuit cable connection screw/bolt M3.5
Tightening torque Nm 1.2
06/16/2021 Eaton 139556 ED2021 V80.0 EN 2 / 12