Data Sheet

DATASHEET - DILM185A/22(RAC240)
Contactor, 380 V 400 V 90 kW, 2 N/O, 2 NC, RAC 240: 190 - 240 V 50/60 Hz,
AC operation, Screw connection
Part no. DILM185A/22(RAC240)
Catalog No. 139537
Alternate Catalog
No.
XTCE185H22B
EL-Nummer
(Norway)
4134277
Delivery program
Product range Contactors
Application Contactors for Motors
Subrange Standard devices greater than 170 A
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Connection technique Screw connection
Rated operational current
AC-3
380 V 400 V I
e
A 185
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 337
enclosed I
th
A 245
Conventional free air thermal current, 1 pole
open I
th
A 685
enclosed I
th
A 625
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 55
380 V 400 V P kW 90
660 V 690 V P kW 140
1000 V P kW 108
AC-4
220 V 230 V P kW 41
380 V 400 V P kW 75
660 V 690 V P kW 102
1000 V P kW 77
Contact sequence
Can be combined with auxiliary contact DILM1000-XHI…
Actuating voltage RAC 240: 190 - 240 V 50/60 Hz
Voltage AC/DC AC operation
Contacts
N/O = Normally open 2 N/O
N/C = Normally closed 2 NC
Auxiliary contacts
possible variants at auxiliary contact module fitting options on the side: 2 x DILM1000-XHI(V)11-SI; 2 x DILM1000-XHI11-SA
Side mounting auxiliary contacts
Instructions Interlocked opposing contacts according to IEC/EN 60947-5-1 Appendix L, inside
the auxiliary contact module
06/18/2021 Eaton 139537 ED2021 V80.0 EN 1 / 12