Data Sheet

AC-53 I
e
A 41
Assigned motor rating (Standard connection, In-Line)
at 230 V, 50 Hz P kW 11
at 400 V, 50 Hz P kW 22
at 200 V, 60 Hz P HP 10
at 230 V, 60 Hz P HP 15
at 460 V, 60 Hz P HP 30
Overload cycle to IEC/EN 60947-4-2
AC-53a 41 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts
Short-circuit rating
Type “1” coordination NZMN1-M50/PKZM4-49
Type „2“ coordination (additional with the fuses for coordination type „1“) 3 x 170M3013
Fuse base (number x part no.) 3 x 170H3004
Terminal capacities
Cable lengths
Solid
mm
2
1 x (25 - 70)
2 x (6 - 25)
Stranded
mm
2
1 x (25 - 70)
2 x (6 - 25)
Solid or stranded AWG 1 x (12 - 2/0)
Copper band MM 2 x 9 x 0.8  9 x 9 x 0.8
Tightening torque Nm 6 (≤ 10 mm²); 9 (> 10 mm²)
Screwdriver (PZ: Pozidriv) mm PZ2; 1 x 6 mm
Control cables
Solid
mm
2
1 x (0.5 - 2.5)
2 x (0.5 - 1.0)
Flexible with ferrule
mm
2
1 x (0.5 - 1.5)
2 x (0.5 - 0.75)
Stranded
mm
2
1 x (0.5 - 1.5)
2 x (0.5 - 1.0)
Solid or stranded AWG 1 x (21 - 14)
2 x (21 - 18)
Tightening torque Nm 0.4
Screwdriver mm 0,6 x 3,5
Control circuit
Digital inputs
Control voltage
AC operated V AC 110 V AC - 15 % - 230 V AC +10 %
Current consumption 24 V mA
External 24 V mA 1.6
Current consumption 230 V mA 4
Pick-up voltage x U
s
AC operated V AC 108 - 253
Drop-out voltage x U
s
AC operated V AC 0 - 15
Pick-up time
AC operated ms 250
Drop-out time
AC operated ms 350
Regulator supply
Voltage U
s
V 110 V AC -15 % - 230 V AC +10 %
Current consumption I
e
mA 50
Current consumption at peak performance (close bypass) at 24VDC I
Peak
A/ms 0,6/50
Notes External supply voltage
Relay outputs
Number 2 (TOR, Ready)
06/16/2021 Eaton 134934 ED2021 V80.0 EN 2 / 5