Data Sheet

Supply frequency f
LN
Hz 50/60
Rated operational current I
e
A
AC-53 I
e
A 16
Assigned motor rating (Standard connection, In-Line)
at 230 V, 50 Hz P kW 4
at 400 V, 50 Hz P kW 7.5
at 200 V, 60 Hz P HP 5
at 230 V, 60 Hz P HP 5
at 460 V, 60 Hz P HP 10
Overload cycle to IEC/EN 60947-4-2
AC-53a 16 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts
Short-circuit rating
Type “1” coordination PKM0-16 (+ CL-PKZ0)
Type „2“ coordination (additional with the fuses for coordination type „1“) 3 x 170M1364
Fuse base (number x part no.) 3 x 170H1007
Terminal capacities
Cable lengths
Solid
mm
2
1 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule
mm
2
1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded
mm
2
1 x 16
Solid or stranded AWG 18 - 6
Tightening torque Nm 3.2
Screwdriver (PZ: Pozidriv) mm PZ2; 1 x 6 mm
Control cables
Solid
mm
2
1 x (0.5 - 2.5)
2 x (0.5 - 1.0)
Flexible with ferrule
mm
2
1 x (0.5 - 1.5)
2 x (0.5 - 0.75)
Stranded
mm
2
1 x (0.5 - 1.5)
2 x (0.5 - 1.0)
Solid or stranded AWG 1 x (21 - 14)
2 x (21 - 18)
Tightening torque Nm 1.2
Screwdriver mm 0,8 x 5,5
1 x 6
Control circuit
Digital inputs
Control voltage
AC operated V AC 110 V AC - 15 % - 230 V AC +10 %
Current consumption 24 V mA
External 24 V mA 1.6
Current consumption 230 V mA 4
Pick-up voltage x U
s
AC operated V AC 108 - 253
Drop-out voltage x U
s
AC operated V AC 0 - 15
Pick-up time
AC operated ms 250
Drop-out time
AC operated ms 350
Regulator supply
Voltage U
s
V 110 V AC -15 % - 230 V AC +10 %
Current consumption I
e
mA 50
Notes External supply voltage
06/16/2021 Eaton 134930 ED2021 V80.0 EN 2 / 5