Data Sheet

Current consumption I
e
mA 50
Current consumption at peak performance (close bypass) at 24VDC I
Peak
A/ms 0,6/50
Notes External supply voltage
Relay outputs
Number 2 (TOR, Ready)
Voltage range V AC 24 V AC/DC
250 V AC
AC-11 current range A 1 A, AC-11
Soft start function
Ramp times
Acceleration s 1 - 30
Deceleration s 0 - 30
Start voltage (= turn-off voltage) % 30 100
Start pedestal % 30 - 100
Fields of application
Fields of application Soft starting of three-phase asynchronous motors
1-phase motors ●
3-phase motors ✓
Functions
Fast switching (semiconductor contactor) - (minimum ramp time 1s)
Soft start function ✓
Reversing starter External solution required
Suppression of closing transients ✓
Suppression of DC components for motors ✓
Potential isolation between power and control sections ✓
Notes
Rated impulse withstand voltage:
• 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
• Applies for control circuit/power section/enclosure
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 135
Heat dissipation per pole, current-dependent P
vid
W 0
Equipment heat dissipation, current-dependent P
vid
W 24
Static heat dissipation, non-current-dependent P
vs
W 24
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -5
Operating ambient temperature max. °C 40
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
06/18/2021 Eaton 134921 ED2021 V80.0 EN 3 / 5