Data Sheet
Rated operational current I
e
A
AC-53 I
e
A 12
Assigned motor rating (Standard connection, In-Line)
at 230 V, 50 Hz P kW 3
at 400 V, 50 Hz P kW 5.5
at 200 V, 60 Hz P HP 3
at 230 V, 60 Hz P HP 3
at 460 V, 60 Hz P HP 10
Overload cycle to IEC/EN 60947-4-2
AC-53a 12 A: AC-53a: 3 - 5: 75 - 10
Internal bypass contacts ✓
Short-circuit rating
Type “1” coordination PKM0-12 (+ CL-PKZ0)
Type „2“ coordination (additional with the fuses for coordination type „1“) 3 x 170M1362
Fuse base (number x part no.) 3 x 170H1007
Terminal capacities
Cable lengths
Solid
mm
2
1 x (0.75 - 4)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 18 - 10
Tightening torque Nm 1.2
Screwdriver (PZ: Pozidriv) mm PZ2; 1 x 6 mm
Control cables
Solid
mm
2
1 x (0.75 - 4)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Solid or stranded AWG 18 - 10
Tightening torque Nm 1.2
Screwdriver mm 0,8 x 5,5
1 x 6
Control circuit
Digital inputs
Control voltage
DC-operated V DC 24 V DC +10 %/- 15 %
AC operated V AC 24 V AC +10 %/- 15 %
Current consumption 24 V mA
External 24 V mA 1.6
Pick-up voltage x U
s
DC-operated V DC 17.3 - 27
AC operated V AC 17.3 - 27
Drop-out voltage x U
s
DC operated V DC 0 - 3
AC operated V AC 0 - 3
Pick-up time
DC operated ms 250
AC operated ms 250
Drop-out time
DC operated ms 350
Regulator supply
Voltage U
s
V 24 V AC/DC +10 %/- 15 %
Current consumption I
e
mA 50
Notes External supply voltage
Relay outputs