Data Sheet

DATASHEET - DILEM12-10-G(24VDC)
Contactor, 24 V DC, 3 pole, 380 V 400 V, 5.5 kW, Contacts N/O = Normally
open= 1 N/O, Screw terminals, DC operation
Part no. DILEM12-10-G(24VDC)
Catalog No. 127132
Alternate Catalog
No.
XTMC12A10TD
EL-Nummer
(Norway)
4110190
Delivery program
Product range Contactors
Application Contactors for Motors
Mini Contactors for Motors and Resistive Loads
Subrange DILEM contactors
Utilization category AC-1: Non-inductive or slightly inductive loads, resistance furnaces
NAC-3: Normal AC induction motors: starting, switch off during running
AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Connection technique Screw terminals
Description With auxiliary contact
Number of poles 3 pole
Rated operational current
AC-3
380 V 400 V I
e
A 12
AC-1
Conventional free air thermal current, 3 pole, 50 - 60 Hz
Open
at 40 °C I
th
=I
e
A 22
Max. rating for three-phase motors, 50 - 60 Hz
AC-3
220 V 230 V P kW 3
380 V 400 V P kW 5.5
660 V 690 V P kW 4
AC-4
220 V 230 V P kW 1.5
380 V 400 V P kW 3
660 V 690 V P kW 3
Contacts
N/O = Normally open 1 N/O
Contact sequence
Instructions Integrated diode-resistor combination
For use with …DILEM
…DILE
Actuating voltage 24 V DC
Voltage AC/DC DC operation
Technical data
General
Standards IEC/EN 60947, VDE 0660, CSA, UL
Lifespan, mechanical Operations
x 10
6
5
Maximum operating frequency
Mechanical Ops./h 9000
electrical (Contactors without overload relay) Operations/h Page 05/070
Climatic proofing Damp heat, constant, to IEC 60068-2-78
06/18/2021 Eaton 127132 ED2021 V80.0 EN 1 / 11