Data Sheet
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 25
Altitude m Max. 2000
Terminal capacity main cable
Screw terminals
Solid
mm
2
1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228
mm
2
1 x (1 - 6)
2 x (1 - 6)
Solid or stranded AWG 14 - 10
Stripping length mm 10
Specified tightening torque for terminal screws
Main cable Nm 1.7
Control circuit cables Nm 1
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V AC 690
Rated uninterrupted current = rated operational current I
u
= I
e
A 4
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 0.9
Lifespan, mechanical Operations
x 10
6
0.05
Lifespan, electrical (AC-3 at 400 V)
Lifespan, electrical Operations
x 10
6
0.05
Max. operating frequency Ops/h 60
Motor switching capacity
AC-3 (up to 690V) A 4
AC-4 cycle operation
Minimum current flow times ms 500 (Class 5)
700 (Class 10)
900 (Class 15)
1000 (Class 20)
Minimum cut-out periods ms 500
Note ms In AC-4 cycle operation, going below the minimum current flow time can cause
overheating of the load (motor).
For all combinations with an SWD activation, you need not adhere to the minimum
current flow times and minimum cut-out periods.
Trip blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55
Setting range of overload releases x I
u
0.25 - 1
short-circuit release Basic device, fixed: 15.5 x I
u
Trip block, fixed: 15.5 x I
r
delayed approx. 60 ms
Short-circuit release tolerance ± 20%
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
06/18/2021 Eaton 121732 ED2021 V80.0 EN 2 / 8