Data Sheet

DATASHEET - PKE12/XTU-4
Motor-protective circuit-breaker, Complete device with standard knob,
Electronic, 1 - 4 A, With overload release
Part no. PKE12/XTU-4
Catalog No. 121732
Alternate Catalog
No.
XTPE004BCSNL
EL-Nummer
(Norway)
4355181
Delivery program
Product range PKE motor protective circuit-breakers with electronic wide-range overload
protection up to 32 A
Basic function Motor protection
Motor protection for heavy starting duty
Single unit/Complete unit Complete device with standard knob
Notes Also suitable for motors with efficiency class IE3.
Connection technique Screw terminals
Setting range of overload releases I
r
A 1 - 4
Function With overload release
Rated uninterrupted current = rated operational current I
u
= I
e
A 4
Motor rating
AC-3
220 V 230 V 240 V P kW 0.75
380 V 400 V 415 V P kW 1.5
440 V P kW 1.5
500 V P kW 2.2
660 V 690 V P kW 3
Motor output/rated motor current
Motor rating Rated motor
current
AC-3
220 V
230 V
240 V
380 V
400 V
415 V
440 V 500 V 660 V
690 V
P I I I I I
kW A A A A A
0.18 1.04 - - - -
0.25 1.4 - - - -
0.37 2 1.1 1.02 - -
0.55 2.7 1.5 1.39 1.2 -
0.75 3.2 1.9 1.68 1.5 1.1
1.1 - 2.6 2.41 2.1 1.5
1.5 - 3.6 3.28 2.9 2.1
2.2 - - - 4 2.9
3 - - - - 3.8
Technical data
General
Standards IEC/EN 60947, VDE 0660,UL, CSA
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Storage °C - 40 - 80
Open °C -25 - +55
Enclosed °C - 25 - 40
06/18/2021 Eaton 121732 ED2021 V80.0 EN 1 / 8

Summary of content (8 pages)