Datasheet

Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Storage °C - 40 - 80
Open °C -25 - +55
Enclosed °C - 25 - 40
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 g 25
Altitude m Max. 2000
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V AC 690
Rated uninterrupted current = rated operational current I
u
= I
e
A 32
Rated frequency f Hz 40 - 60
Max. operating frequency Ops/h 60
Motor switching capacity
AC-3 (up to 690V) A 32
AC-4 cycle operation
Minimum current flow times ms 500 (Class 5)
700 (Class 10)
900 (Class 15)
1000 (Class 20)
Minimum cut-out periods ms 500
Note ms In AC-4 cycle operation, going below the minimum current flow time can cause
overheating of the load (motor).
For all combinations with an SWD activation, you need not adhere to the minimum
current flow times and minimum cut-out periods.
Trip blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55
Setting range of overload releases x I
u
0.25 - 1
short-circuit release Trip block, fixed: 15.5 x I
r
delayed approx. 60 ms
Short-circuit release tolerance ± 20%
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 32
Heat dissipation per pole, current-dependent P
vid
W 1.3
Equipment heat dissipation, current-dependent P
vid
W 3.9
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
06/18/2021 Eaton 121726 ED2021 V80.0 EN 2 / 4