Data Sheet
Technical data
General
Standards IEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
DC operated Operations
x 10
6
10
Operating frequency, mechanical
DC operated Operations/h 5000
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +60
Enclosed °C - 25 - 40
Storage °C - 40 - 80
Mounting position
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 10
Auxiliary contacts
N/O contact g 7
N/C contact g 5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contact g 6.9
Auxiliary contacts
N/O contact g 5.3
N/C contact g 3.5
Degree of Protection IP00
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof
Altitude m Max. 2000
Weight
DC operated kg 0.534
Screw connector terminals
Terminal capacity main cable
Solid
mm
2
1 x (0.75 - 16)
2 x (0.75 - 10)
Flexible with ferrule
mm
2
1 x (0.75 - 16)
2 x (0.75 - 10)
Stranded
mm
2
1 x 16
Solid or stranded AWG single 18 - 6, double 18 - 8
Stripping length mm 10
Terminal screw M5
Tightening torque Nm 3.2
Tool
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
1 x 6
Terminal capacity control circuit cables
Solid
mm
2
1 x (0.75 - 4)
2 x (0.75 - 2.5)
Flexible with ferrule
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
06/18/2021 Eaton 112442 ED2021 V80.0 EN 2 / 13