Datasheet

21.06.2012 HPL-ED2012 V1.1 DE 4 / 11
konventioneller thermischer Strom 1-polig
offen I
th
A 100
gekapselt I
th
A 90
AC-3
Bemessungsbetriebsstrom
offen, 3-polig, 50 - 60 Hz
220 V 230 V I
e
A 38
240 V I
e
A 38
380 V 400 V I
e
A 38
415 V I
e
A 38
440 V I
e
A 38
500 V I
e
A 38
660 V 690 V I
e
A 22.5
Bemessungsbetriebsleistung P kW
220 V 230 V P kW 11
240 V P kW 12
380 V 400 V P kW 18.5
415 V P kW 20
440 V P kW 21
500 V P kW 24
660 V 690 V P kW 21
AC-4
offen, 3-polig, 50 - 60 Hz
230 V I
e
A 15
240 V I
e
A 15
400 V I
e
A 15
415 V I
e
A 15
440 V I
e
A 15
500 V I
e
A 15
690 V I
e
A 12
Bemessungsbetriebsleistung P kW
230 V P kW 4
240 V P kW 4.5
400 V P kW 7
415 V P kW 7.5
440 V P kW 8
500 V P kW 9
690 V P kW 10
Gleichspannung
Bemessungsbetriebsstrom I
e
offen
DC-1
60 V I
e
A 40
110 V I
e
A 40
220 V I
e
A 40
440 V I
e
A 2.9
DC-3
60 V I
e
A 40
110 V I
e
A 40
220 V I
e
A 25
440 V I
e
A 0.6
DC-5
60 V I
e
A 40
110 V I
e
A 40