Data Sheet

Approvals EAC
Dimensions (W x H x D) mm 107.5 (6 TE) x 90 x 72
Weight kg 0.35
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(accessories)
Times
Inputs
Max. duration of external test pulde ms 1
Semi-conductor output
Off test pulse ms < 1
Off-delay ms < 1
Terminal capacities
Solid
mm
2
0.2/4 (AWG 22 - 12)
Flexible with ferrule
mm
2
0.2/2.5 (AWG 22 - 12)
Standard screwdriver mm 0.8 x 3.5
Max. tightening torque Nm 0.6
Climatic environmental conditions
Operating ambient temperature °C -25 to + 55
cold as per IEC 60068-2-1
heat as per IEC 60068-2-2
Damp heat – constant to IEC 60068-2-78 – cyclical to ICE 60068-2-30
Condensation Take appropriate measures to prevent condensation
LCD display (clearly legible) °C 0 - 55
Ambient temperature
Storage ϑ °C -40 - +55
relative humidity % 5 - 95
in accordance with IEC 60068-2-30, IEC 60068-2-78
Non-condensing
Air pressure (operation) hPa 795 - 1080
Ambient conditions, mechanical
Degree of protection IP20 (IEC/EN 60529, EN50178, VBG 4)
Constant amplitude 0.15 mm Hz
constant amplitude Hz 10 - 57 (0.15 mm)
constant acceleration Hz 57 - 150 (2g)
Vibrations 3,5 mm / 1 g Hz In accordance with IEC 60068-2-6
Mechanical shock resistance g 18 shocks
Sinusoidal 15 g/11 ms
according to IEC 60068-2-27
Drop to Drop height mm 50
(IEC/EN 60068-2-31)
Free fall, packaged m 0,3
(IEC/EN 61131-2)
Electromagnetic compatibility (EMC)
Electromagnetic compatibility As per ICE 62061, increased EMC requirements for safety-relevant functions
Overvoltage category/pollution degree III/2
Electrostatic discharge (ESD)
applied standard nach IEC/EN 61000-4-2
Air discharge kV 15
Contact discharge kV 8
Electromagnetic fields (RFI) V/m 30
to IEC EN 61000-4-3
Radio interference suppression EN 55011 Class B, EN 55022 Class B
Burst kV according to IEC/EN 61000-4-4
Supply cables: 4
Signal cables: 4
power pulses (Surge) 2 kV (supply cables, symmetrical)
4 kV (semi-conductor outputs, symmetrical)
In accordance with IEC 62061
Immunity to line-conducted interference V 20, in accordsnce with IEC/EN 61000-4-6
Insulation resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142, EN 60664-1:2003
Insulation resistance EN 50178
06/16/2021 Eaton 111017 ED2021 V80.0 EN 2 / 8