Data Sheet

DC-betätigt P300
General Use
AC V 600
AC A 10
DC V 250
DC A 1
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 5
max. Fuse A 125
max. CB A 125
480 V High Fault
SCCR (fuse) kA 10/100
max. Fuse A 125/70 Class J
SCCR (CB) kA 10/65
max. CB A 50/32
600 V High Fault
SCCR (fuse) kA 10/100
max. Fuse A 125/100 Class J
SCCR (CB) kA 10/22
max. CB A 50/32
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3phase, 277V 60Hz 1phase A 40
600V 60Hz 3phase, 347V 60Hz 1phase A 40
Incandescent Lamps (Tungsten)
480V 60Hz 3phase, 277V 60Hz 1phase A 40
600V 60Hz 3phase, 347V 60Hz 1phase A 40
Resistance Air Heating
480V 60Hz 3phase, 277V 60Hz 1phase A 40
600V 60Hz 3phase, 347V 60Hz 1phase A 40
Refrigeration Control (CSA only)
LRA 480V 60Hz 3phase A 240
FLA 480V 60Hz 3phase A 40
LRA 600V 60Hz 3phase A 180
FLA 600V 60Hz 3phase A 30
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3phase A 150
FLA 480V 60Hz 3phase A 25
Elevator Control
200V 60Hz 3phase HP 3
200V 60Hz 3phase A 11
240V 60Hz 3phase HP 5
240V 60Hz 3phase A 15.2
480V 60Hz 3phase HP 10
480V 60Hz 3phase A 14
600V 60Hz 3phase HP 15
600V 60Hz 3phase A 17
Daten für Bauartnachweis nach IEC/EN 61439
Technische Daten für Bauartnachweis
Bemessungsstrom zur Verlustleistungsangabe I
n
A 45
Verlustleistung pro Pol, stromabhängig P
vid
W 4.4
Verlustleistung des Betriebsmittels, stromabhängig P
vid
W 13.2
Verlustleistung statisch, stromunabhängig P
vs
W 2.1
16.06.2021 Eaton 109826 ED2021 V80.0 DE 5 / 10