Data Sheet
Elektromagnetische compatibiliteit
Storingsemissie Conform EN 61131-1
Storingsongevoeligheid Conform EN 61131-1
Goedgekeurde vermogensspecificaties
Schakelvermogen
Max. motorvermogen
3-fase
200 V
208 V
HP 20
230 V
240 V
HP 25
460 V
480 V
HP 50
575 V
600 V
HP 60
1-fase
115 V
120 V
HP 5
230 V
240 V
HP 15
General use A 88
Short Circuit Current Rating SCCR
Basic Rating
SCCR kA 10
max. Fuse A 250
max. CB A 250
480 V High Fault
SCCR (zekering) kA 30/100
max. Fuse A 250/150 Class J
SCCR (CB) kA 65
max. CB A 100
600 V High Fault
SCCR (zekering) kA 30/100
max. Fuse A 250/150 Class J
SCCR (CB) kA 30
max. CB A 250
Special Purpose Ratings
Electrical Discharge Lamps (Ballast)
480V 60Hz 3fase, 277V 60Hz 1fase A 88
600V 60Hz 3fase, 347V 60Hz 1fase A 88
Incandescent Lamps (Tungsten)
480V 60Hz 3fase, 277V 60Hz 1fase A 88
600V 60Hz 3fase, 347V 60Hz 1fase A 88
Resistance Air Heating
480V 60Hz 3fase, 277V 60Hz 1fase A 88
600V 60Hz 3fase, 347V 60Hz 1fase A 88
Definite Purpose Ratings (100,000 cycles acc. to UL 1995)
LRA 480V 60Hz 3fase A 432
FLA 480V 60Hz 3fase A 72
Elevator Control
200V 60Hz 3fase HP 10
200V 60Hz 3fase A 32.2
240V 60Hz 3fase HP 15
240V 60Hz 3fase A 42
480V 60Hz 3fase HP 30
480V 60Hz 3fase A 40
600V 60Hz 3fase HP 40
600V 60Hz 3fase A 41
17.06.2021 Eaton 107670 ED2021 V80.0 NL 5 / 13