Data Sheet

24 V I
e
A 6
220 V 230 V 240 V I
e
A 6
380 V 400 V 415 V I
e
A 4
DC-13
24 V I
e
A 3
110 V I
e
A 0.8
220 V I
e
A 0.3
Supply frequency Hz max. 400
Short-circuit rating to IEC/EN 60947-5-1
max. fuse A gG/gL 6
Rated conditional short-circuit current kA 1
Mechanical variables
Lifespan, mechanical Operations
x 10
6
1
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
Standard-action contact g 10
Operating frequency Operations/h ≦ 800
Actuation
Mechanical
Actuating force at beginning/end of stroke N 25/15 (plug-in/pull-out)
Mechanical holding force acc. to GS-ET-19 (04/2004)
XG, XW, XNG N 1700
XWA, XFG, XF N 1600
XNW N 1200
Electromechanical
For magnet
Power consumption
at 120 V AC VA 8
at 230 V AC VA 11
at 24 V DC W 8
Pick-up and drop-out values x U
s
0.85 - 1.1
Magnet duty factor % ED 100
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6
Heat dissipation per pole, current-dependent P
vid
W 0.13
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 40
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
06/18/2021 Eaton 106830 ED2021 V80.0 EN 2 / 4