DATASHEET - DILM150-XRL
Reversing wiring kit DILM80 to DILM150
Part no. DILM150-XRL
Catalog No. 101681
Alternate Catalog
No.
XTCEXRLG
EL-Nummer
(Norway)
4137736
Delivery program
Product range Accessories
Accessories Wiring accessories
Description Main current wiring for reversing combinations
For use with DILM80
DILM95
DILM115
DILM150
DILMF80
DILMF95
DILMF115
DILMF150
For use with Reversing wiring kit DILM80 to DILM150
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 225
Heat dissipation per pole, current-dependent P
vid
W 2.9
Equipment heat dissipation, current-dependent P
vid
W 8.7
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 60
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
06/18/2021 Eaton 101681 ED2021 V80.0 EN 1 / 2

Summary of content (2 pages)