Functions overview for actuators in Comfort Mode (by means of MRF-Software and PC) - continued
For each sensor assigned (max. 15 sensor per actuator) the following different functions can be selected:
Shutters/blinds actuator functions that can be selected in Comfort Mode
Blinds (Standard in Basic-Mode)
Slat Up / Down or Stop and Open/Close for the time of the preset operation time
Shutters
Stop and Open/Close for the time of the preset operation time
Shutters with Open function
Stop and Open/Close (with short opening) for the time of the preset operation time
Open
Open for the time of the preset operation time
Close
Close for the time of the preset operation time
Stop
Stop command
Sequence control
Changes upon each command in the following order: Open - Stop – Close – Stop – Open …
Security upon switching ON (with CJAU-01/02 only)
Moves to the security position upon an ON command
Security upon switching OFF (with CJAU-01/02 only)
Moves to the security position upon an OFF command
Acknowledgement of security position
Acknowledges a current security position
No function
As indicated
Functions available:
Operation time of the blinds/shutters: 1 second to 1 hour (0 seconds and push-button operation with CJAU-01/02
only)
Command time for a long push at the button: 1 to 5 seconds
Security position: Top/bottom/stop (with CJAU-01/02 only)
Cycle time of security: 10 minutes to 18 hours (cyclical reception switched off with CJAU-01/02 only)