5. "Heating actuator for electrical panel" with assigned "Room Manager Room1", specifiaction of the set-point value in
“COMFORT” mode through the handwheel on the electrical panel, specification of the set-point value in “ECO” mode
through the Room Manager, with the window contact and Room Manager being linked
Application: Office with individual on-site control during office hours, automatic reduction outside office
hours
Operating mode on the RM "Auto or Comfort"
Set-point temperature Auto in Comfort time
Handwheel on the electrical panel
or
Set-point temperature Comfort Handwheel on the electrical panel
Real temperature: Temperature sensor integrated in the electrical panel
LED Heating (red): ON when heating is requested
LED ECO (green): OFF
Operating mode on the RM "Standby, Night, Anti-freeze, Holiday, Window open"
Set-point value Auto except in Depending on the setting of the RM (pre-setting 18°C)
Comfort time or
Set-point value Standby Depending on the setting of the RM (pre-setting 20°C)
or
Set-point value Night Depending on the setting of the RM (pre-setting 18°C)
or
Set-point value Anti-freeze, Holiday,
Window open Depending on the setting of the RM (pre-setting 10°C)
Real temperature: Internal sensor Room Manager Room 1
LED Heating (red): ON when heating is requested
LED ECO (geen): ON,
Comfort extension can now be activated (pre-setting 3 hours).
When comfort extension is active, the set-point temperature of the handwheel on the electrical
panel will be applied.
Operating mode on RM "OFF"
Set-point temperature: No specification of a set-point value as "OFF"
Real temperature: Internal sensor Room Manager Room 1, no impact as OFF
LED Heating (red): OFF
LED ECO (green): Flashing (1x every 10s)
Comfort extension not possible!