Datasheet
EATON RF SYSTEM
62
4. "Heating actuator for electrical panels" with assigned "Room Manager Room1", specification of set-point values (via
operating modes) and real temperature (internal Room1) from the Room Manager, with window contact and Room
Manager being linked
Application: Typical individual room control with a time/temperature profile and operating modes, holiday
function included
Operating mode on the RM "Auto or Comfort"
Set-point temperature Auto in Depending on the setting of the RM (pre-setting 21°C)
Comfort time or
Set-point temperature Comfort Depending on the setting of the RM (pre-setting 21°C)
Real temperature: Internal sensor Room Manager Room 1
LED Heating (red): ON when heating is requested
LED ECO (green): OFF
Operating mode on the RM "Standby, Night, Anti-freeze, Holiday, Window open"
Set-point value Standby Depending on the setting of the RM (pre-setting 20°C)
or
Set-point value Night Depending on the setting of the RM (pre-setting 18°C)
or
Set-point value anti-freeze, holiday,
Window open Depending on the setting of the RM (pre-setting 10°C)
Real temperature: Internal sensor Room Manager Room 1
LED Heating (red): ON when heating is requested
LED ECO (green): ON,
Comfort extension can now be activated (pre-setting 3 hours).
When comfort extension is active, the set-point temperature of the handwheel on the electrical panel will
be applied.