Datasheet

EATON RF SYSTEM
56
VOC Air Quality Sensor 0-10VDC CSEZ-01/16
Technical Specifications
Power supply 15-24VDC ±10%
Power consumption max. 50mA/24VDC
All connections Screw-type terminals, max. 1.5mm
2
Sensor Mixed gas VOC
Pre-heating time of sensor approx. 30 min
Output voltage 0-10VDC linear to air quality
max. 10mA
Degree of protection IP20
Operating temperature -10 to +50°C
Permitted relative air humidity max. 85%rF
Storage/transportation temp. -25 to +70°C
Colour of the enclosure similar to RAL9010
Dimensions of the enclosure HxWxD - 84.5 x 84.5x 25mm
Approval Printed onto the device
1 person in the room
plus cigarette smoke
Window is
closed
5 people enter
the room
People leave the room
Window is opened Window is opened
Detection of cleaning agents
Comparison of Air Quality Sensor (CSEZ-01/16) and conventional CO2 sensor
Output voltage in V
Hours
Conventional CO2 sensor
Air Quality Sensor (CSEZ-01/16)