Datasheet
EATON RF SYSTEM
4
Wiring Examples for Switching Actuator CSAU-01/03
e.g. lamps,
pumps,
fans,
sound signal
emitters
e.g. electric heat-
ing (heating con-
tactor)
e.g. electric
sauna
Switching fluorescent lamps with a CSAU-01/03 actuator
SA cycles Total capacitor value
37000 25µF
15000 55µF
7000 90µF
4000 107µF
2000 133µF
The numbers of SA cycles specified are approximate values and may vary depending on the local conditions prevailing in each case. The
total capacitor value is the sum of the individual capacitor values according to the type and number of fluorescent lamps compensated in
parallel (see table below). The max. load current of the actuator must not be exceeded. The max. number of cycles selected depends on the
type of application and hence determines the number of fluorescent lamps to be switched via an actuator.
Lamp capacity Capacitor / Compensation in parallel
4-13W 2uF
15-40W 4,5uF
58W 7uF
The above mentioned values are given by the manufacturers of fluorescent lamps and ballasts. Subject to changes without guarantee.