Datasheet

EATON RF SYSTEM
35
Room Manager CRMA-00/01 up to CRMA-00/10, CRMA-00/19 up to CRMA-00/122 (without Bluetooth),
CRMA-00/11 up to CRMA-00/18 (with Bluetooth)
Technical Specifications
Power supply 230VAC/50Hz
Power consumption:
CRMA-00/01 up to CRMA-00/10 1VA (without Bluetooth)
CRMA-00/19 up to CRMA-00/22 1VA (without Bluetooth)
CRMA-00/11 up to CRMA-00/18 1.5VA (with Bluetooth,
Bluetooth activated)
Pre-protection Power circuit breaker 16A, charateristic C
Frequency 868,300MHz
Type of transmission Bi-directional, via coded telegrams
Indoor range Typically 30 - 50m, 2 walls + 1 ceiling
(depending on wall thickness and material !!)
Power reserve - time: 24h
Interfaces IR-interface for system-update
EATON RF for configuration/operation
Degree of protection IP20
Degree of soiling 2
Operating temperature +5 to +45°C
Storage/transportation temp. -25 to +70°C
Colour of the enclosure - similar to RAL9006:
CRMA-00/01, CRMA-00/03 up to CRMA-00/06,
CRMA-00/11 up to CRMA-00/14, CRMA-00/19 up to
CRMA-00/22
- similar to RAL9016:
CRMA-00/02, CRMA-00/07 up to CRMA-00/10,
CRMA-00/15 up to CRMA-00/18
Dimensions of the enclosure HxWxD - 158 x 116 x 27 mm
Approval Printed onto the device
Notes on the use of an internal temperature sensor (room1)
RECOMMENDATIONS for installation:
- fix the RM approx. 1.5m above floor level
-
at a distance of 0.2m min. from door frames (draft)
- install the Room Manager opposite the heating
source, if possible
- keep ventilation slots of the room controller clear
and clean
DO NOT install the device
- at/next to a window
- behind curtains/coat racks
- behind doors
-
above/next to heaters, chimneys, air conditioning …
- above/next to electrical devices (TV, computer...)
- on external walls
- exposed to direct sunlight
- exposed to draft (ventilation)
- on condensing walls
CRMA-00/02