Datasheet

EATON RF SYSTEM
34
Room Controller CRCA-00/04, CRCA-00/05, CRCA-00/06, CRCA-00/07
Technical Specifications
Power supply 3V via 2x LR03 (AAA)
CRCA-00/04, CRCA-00/05, CRCA-00/06, CRCA-00/07
Channel A:
Temperature range 0 - 40°C
Standard setting 21°C, +/- 3°C variable by adjustment wheel
Hysteresis +/- 0.5°C
CRCA-00/05, CRCA-00/07
Channel B:
Permitted relative air humidity 0-100 %
Operating range 10-95%
Accuracy within the measuring
range +/-5% rF
Long-term stability
at 20-30°C / 20-80% rel.hum. Drift approx.1.5% per year
Response time approx. 15 seconds
Standard setting 0 - 40°C
Standard setting relative humidity 50%
Hysteresis +/- 5%
Frequency 868,300 MHz
Type of transmission Bi-directional, via coded telegrams
Indoor range Typically 30 - 50m, 2 walls + 1 ceiling
(depending on wall thickness and material !!)
Service life of the battery Approx. 5 - 7 years,
depending on the type of battery
Degree of protection IP20
Degree of soiling 2
Operating temperature 0 to +40°C
Storage/transportation temp. -25 to +70°C
Colour of the frame White, similar to RAL9010
Dimensions HxWxD - 85 x 86 x 26mm
Approval Printed onto the device
Note RECOMMENDATIONS for installation:
- fix the RC approx. 1.5m above floor level
-
at a distance of 0.2m min. from door frames (draft)
- install the room controller opposite the heat
source, if possible
- keep ventilation slots of the room controller clear
and clean
DO NOT install the device
- at/next to a window
- behind curtains/coat racks
- behind doors
-
above/next to heaters, chimneys, air conditioning …
- above/next to electrical devices (TV, computer...)
- on external walls
- exposed to direct sunlight
- exposed to draft (ventilation)
- on condensing walls