Data Sheet
Technical data
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204
Switch-disconnector according to IEC/EN 60947-3
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +50
Enclosed °C -25 - +40
Overvoltage category/pollution degree III/3
Rated impulse withstand voltage U
imp
V AC 6000
Mechanical shock resistance g 15
Mounting position As required
Contacts
Electrical characteristics
Rated operational voltage U
e
V AC 690
Rated uninterrupted current I
u
A 100
Note on rated uninterrupted current !
u
Rated uninterrupted current I
u
is specified for max. cross-section.
Load rating with intermittent operation, class 12
AB 25 % DF x I
e
2
AB 40 % DF x I
e
1.6
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A gG/gL 100
Rated short-time withstand current (1 s current) I
cw
A
rms
1700
Note on rated short-time withstand current lcw Current for a time of 1 second
Rated conditional short-circuit current I
q
kA 2
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3 A 950
Rated breaking capacity cos ϕ to IEC 60947-3 A
230 V A 760
400/415 V A 740
500 V A 590
690 V A 420
Safe isolation to EN 61140
between the contacts V AC 440
Current heat loss per contact at I
e
W 7.5
Current heat loss per auxiliary circuit at I
e
(AC-15/230 V) CO 7.5
Lifespan, mechanical Operations
x 10
6
> 0.5
Maximum operating frequency Operations/h 1200
AC
AC-3
Rating, motor load switch P kW
220 V 230 V P kW 22
230 V Star-delta P kW 30
400 V 415 V P kW 30
400 V Star-delta P kW 45
500 V P kW 30
500 V Star-delta P kW 45
690 V P kW 15
690 V Star-delta P kW 22
Rated operational current motor load switch
230 V I
e
A 71
230 V star-delta I
e
A 100
400V 415 V I
e
A 55
01/09/2020 Eaton 096942 ED2019 V63.0 EN 2 / 5