Data Sheet
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A gG/gL 100
Rated short-time withstand current (1 s current) I
cw
A
rms
1700
Note on rated short-time withstand current lcw Current for a time of 1 second
Rated conditional short-circuit current I
q
kA 2
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3 A 950
Rated breaking capacity cos ϕ to IEC 60947-3 A
230 V A 760
400/415 V A 740
500 V A 590
690 V A 420
Safe isolation to EN 61140
between the contacts V AC 440
Current heat loss per contact at I
e
W 7.5
Current heat loss per auxiliary circuit at I
e
(AC-15/230 V) CO 7.5
Lifespan, mechanical Operations
x 10
6
> 0.5
Maximum operating frequency Operations/h 1200
AC
AC-3
Rating, motor load switch P kW
220 V 230 V P kW 22
230 V Star-delta P kW 30
400 V 415 V P kW 30
400 V Star-delta P kW 45
500 V P kW 30
500 V Star-delta P kW 45
690 V P kW 15
690 V Star-delta P kW 22
Rated operational current motor load switch
230 V I
e
A 71
230 V star-delta I
e
A 100
400V 415 V I
e
A 55
400 V star-delta I
e
A 95.3
500 V I
e
A 44
500 V star-delta I
e
A 76.2
690 V I
e
A 17
690 V star-delta I
e
A 29.4
AC-21A
Rated operational current switch
440 V I
e
A 100
AC-23A
Motor rating AC-23A, 50 - 60 Hz P kW
230 V P kW 30
400 V 415 V P kW 55
500 V P kW 37
690 V P kW 30
Rated operational current motor load switch
230 V I
e
A 100
400 V 415 V I
e
A 100
500 V I
e
A 55
690 V I
e
A 32
DC
01/09/2020 Eaton 094878 ED2019 V63.0 EN 2 / 4