Data Sheet

Screw terminals
Solid
mm
2
1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228
mm
2
1 x (1 - 6)
2 x (1 - 6)
Solid or stranded AWG 18 - 10
Stripping length mm 10
Specified tightening torque for terminal screws
Main cable Nm 1.7
Control circuit cables Nm 1
Main conducting paths
Rated impulse withstand voltage U
imp
V AC 6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V AC 690
Rated uninterrupted current = rated operational current I
u
= I
e
A 16
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6
Lifespan, mechanical Operations
x 10
6
0.1
Lifespan, electrical (AC-3 at 400 V)
Lifespan, electrical Operations
x 10
6
0.1
Max. operating frequency Ops/h 40
Short-circuit rating
DC
Short-circuit rating kA 60
Motor switching capacity
AC-3 (up to 690V) A 16
DC-5 (up to 250V) A 16 (3 contacts in series)
Trip blocks
Temperature compensation
to IEC/EN 60947, VDE 0660 °C - 5 … 40
Operating range °C - 25 … 55
Temperature compensation residual error for T > 40 °C ≦ 0.25 %/K
Setting range of overload releases x I
u
0.6 - 1
short-circuit release Basic device, fixed: 20 x I
u
Short-circuit release tolerance ± 20%
Phase-failure sensitivity IEC/EN 60947-4-1, VDE 0660 Part 102
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 16
Heat dissipation per pole, current-dependent P
vid
W 2
Equipment heat dissipation, current-dependent P
vid
W 6
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
06/18/2021 Eaton 088917 ED2021 V80.0 EN 2 / 9