Data Sheet

Mechanical shock resistance to IEC 60068-2-27 Half-
sinusoidal
shock 20 ms
g > 10
Vibration resistance acc. to IEC/EN 60068-2-6 Amplitude 1
mm
Hz 36
lifespan Operations
x 10
6
0.5
Terminal capacities
mm
2
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Flexible with ferrules to DIN 46228
mm
2
1 x (0.5 - 1.5)
2 x (0.5 - 1.5)
Terminations Flat terminal with clamping washer
Terminal screw M4
Tightening torque of terminal screw Nm 1.2
Contacts/switching capacity
Rated impulse withstand voltage U
imp
V AC 4000
Rated insulation voltage U
i
V 400
Overvoltage category/pollution degree III/3
Max. short-circuit protective device
Fuseless Type PKZM0-20
Fuse gG/gL A 20
Type of coordination 1
Rated short-circuit current I
q
(= Current r) kA 1
AC-3
Rated operational current
230 V A 15
400 V A 11.5
Rated power P
230 V kW 4
400 V kW 5.5
Rated frequency f Hz 50
Design verification as per IEC/EN 61439
Technical data for design verification
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
Technical data ETIM 7.0
Stats, switches and controllers (EG015840) / Float switch (EC011178)
Suitable for potable water Yes
Suitable for rainwater Yes
Suitable for cooling water Yes
Suitable for faeces Yes
Suitable for domestic wastewater Yes
Suitable for condensate Yes
Suitable for glycol Yes
Measuring range mm
Readable No
With display No
Adjustable differential gap No
Differential range/switch hysteresis mm
Immersing depth mm
Mounting method, vertical Yes
Mounting method, horizontal Yes
Sensor/feeler type Sinking ball
Mounting method Suspended above the pit
06/16/2021 Eaton 088594 ED2021 V80.0 EN 2 / 3