Data Sheet
DC-13 L/R - 100 ms
24 V I
e
A 2
60 V I
e
A 1
110 V I
e
A 0.5
220 V I
e
A 0.25
Lifespan S
Lifespan, mechanical Operations
x 10
6
> 0.1
Lifespan, electrical Operations
x 10
6
0.05
Control circuit reliability Failure rate λ
<10
-8
, < one failure at 100 million operations
(at U
e
= 24 V DC, U
min
= 17 V, I
min
= 5.4 mA)
interlocked opposing contacts yes
Short-circuit rating without welding
Fuseless Type FAZ-B4/1-HI
Fuse A gG/gL 10
Terminal capacities
Solid or flexible conductor, with ferrule
mm
2
0,75 - 2,5
Solid or stranded AWG 18 - 14
Rating data for approved types
Pilot Duty
AC operated A600
DC operated Q300
General Use
AC V 600
AC A 5
DC V 250
DC A 1
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 3.5
Heat dissipation per pole, current-dependent P
vid
W 0.04
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
06/18/2021 Eaton 072896 ED2021 V80.0 EN 2 / 5