Data Sheet
230 V I
e
A 63
400 V 415 V I
e
A 63
500 V I
e
A 63
690 V I
e
A 63
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 63
Voltage per contact pair in series V 60
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current I
e
A 50
Contacts Quantity 1
48 V
Rated operational current I
e
A 50
Contacts Quantity 2
60 V
Rated operational current I
e
A 50
Contacts Quantity 2
120 V
Rated operational current I
e
A 25
Contacts Quantity 3
Control circuit reliability at 24 V DC, 10 mA Fault
probability
H
F
< 10
-5
,< 1 failure in 100,000 switching operations
Terminal capacities
Solid or stranded
mm
2
1 x (2,5 - 35)
2 x (2,5 - 10)
Flexible with ferrules to DIN 46228
mm
2
1 x (1.5 - 25)
2 x (1.5 - 6)
Terminal screw M5
Tightening torque for terminal screw Nm 3
Technical safety parameters:
Notes B10
d
values as per EN ISO 13849-1, table C1
Rating data for approved types
Contacts
Rated operational voltage U
e
V AC 600
Rated uninterrupted current max.
Main conducting paths
General use A 60
Auxiliary contacts
General Use I
U
A 10
Pilot Duty A 600
P 600
Switching capacity
Maximum motor rating
Single-phase
120 V AC HP 3
200 V AC HP 7.5
240 V AC HP 10
Three-phase
200 V AC HP 15
240 V AC HP 15
480 V AC HP 40
600 V AC HP 50
Short Circuit Current Rating SCCR
Basic Rating kA 10
max. Fuse A 150
Terminal capacity
06/16/2021 Eaton 048218 ED2021 V80.0 EN 3 / 6