Data Sheet

Rated operational current I
e
A
AC-14 I
e
380 V 400 V 415 V I
e
A 3
Value applies starting with release 001.
AC--14
440 V I
e
A 3
AC-15
220 V 230 V 240 V I
e
A 3
DC-11
Note Making and breaking conditions to DC13, time constant as stated
L/R max. 15 ms A
24 V I
e
A 1.5
L/R max. 50 ms A 1.2
Conv. thermal current I
th
A 6
Short-circuit rating without welding
Note When supplied directly from mains or transformer > 1000 VA
Max. fuse, make contacts A gG/gL 6
Max. fuse, break contacts A gG/gL 6
Max. overcurrent protective device, 220/230 V Type FAZ-B4/1-HI
Magnet systems
Power consumption
Pick-up AC VA 2
Sealing AC VA 2
Pick-up DC W 1.8
Sealing DC W 1.8
Duty factor % DF 100
Maximum operating frequency Ops/h 4000
Minimum command time
AC ms 50
DC ms 30
Repetition accuracy (deviation) % ≦ 0.5
Recovery time (after 100% time delay) ms 70
Contact changeover time t
u
ms 4
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD)
applied standard IEC/EN 61000-4-2
Air discharge kV 8
Contact discharge kV 6
Electromagnetic fields (RFI)
applied standard IEC/EN 61000-4-3
V/m 80 - 1000 MHz: 10
1.4 - 2 GHz: 3
2.0 - 2.7 GHz: 1
Radio interference suppression EN 55011, Class B (conducted)
EN 55011, Class B (radiated)
Burst kV Supply cables: 2
Signal cables: 1
according to IEC/EN 61000-4-4
power pulses (Surge) 2 kV (symmetrical)
4 kV (asymmetrical)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6
Heat dissipation per pole, current-dependent P
vid
W 1.4
Equipment heat dissipation, current-dependent P
vid
W 0
06/18/2021 Eaton 031888 ED2021 V80.0 EN 3 / 15