Data Sheet
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A gG/gL 35
Rated short-time withstand current (1 s current) I
cw
A
rms
650
Note on rated short-time withstand current lcw Current for a time of 1 second
Rated conditional short-circuit current I
q
kA 1
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3 A 320
Rated breaking capacity cos ϕ to IEC 60947-3 A
230 V A 260
400/415 V A 260
500 V A 240
690 V A 170
Safe isolation to EN 61140
between the contacts V AC 440
Current heat loss per contact at I
e
W 1.1
Current heat loss per auxiliary circuit at I
e
(AC-15/230 V) CO 1.1
Lifespan, mechanical Operations
x 10
6
> 0.5
Maximum operating frequency Operations/h 1200
AC
AC-3
Rating, motor load switch P kW
220 V 230 V P kW 5.5
230 V Star-delta P kW 7.5
400 V 415 V P kW 11
400 V Star-delta P kW 15
500 V P kW 15
500 V Star-delta P kW 18.5
690 V P kW 11
690 V Star-delta P kW 22
Rated operational current motor load switch
230 V I
e
A 23.7
230 V star-delta I
e
A 32
400V 415 V I
e
A 23.7
400 V star-delta I
e
A 32
500 V I
e
A 23.7
500 V star-delta I
e
A 32
690 V I
e
A 14.7
690 V star-delta I
e
A 25.5
AC-23A
Motor rating AC-23A, 50 - 60 Hz P kW
230 V P kW 7.5
400 V 415 V P kW 15
500 V P kW 15
690 V P kW 15
Rated operational current motor load switch
230 V I
e
A 32
400 V 415 V I
e
A 32
500 V I
e
A 26.4
690 V I
e
A 17
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 25
Voltage per contact pair in series V 60
06/16/2021 Eaton 020534 ED2021 V80.0 EN 2 / 4