Data Sheet
2 x (0.5 - 1.5)
Solid or stranded AWG 2 x (18 - 12)
Terminal screw M3.5
Tightening torque Nm 1.2
Stripping length mm 8
Tools
Pozidriv screwdriver Size 2
Standard screwdriver mm 0.8 x 5.5
Rated insulation voltage U
i
V AC 500
Rated operational voltage U
e
V AC 500
Safe isolation to EN 61140
between the auxiliary contacts V AC 250
Conventional thermal current I
th
A 6
Rated operational current I
e
A
AC-15
Make contact
120 V I
e
A 1.5
220 V 230 V 240 V I
e
A 1.5
380 V 400 V 415 V I
e
A 0.7
500 V I
e
A 0.5
Break contact
120 V I
e
A 1.5
220 V 230 V 240 V I
e
A 1.5
380 V 400 V 415 V I
e
A 0.7
500 V I
e
A 0.5
DC L/R ≦ 15 ms
Switch-on and switch-off conditions based on DC-13, time constant as specified.
24 V I
e
A 0.9
60 V I
e
A 0.75
110 V I
e
A 0.4
220 V I
e
A 0.2
Short-circuit rating without welding
max. fuse A gG/gL 4
Notes
Notes Ambient air temperature: Operating range to IEC/EN 60947, PTB: -5°C to +50°C
Main circuits terminal capacity solid and flexible conductors with ferrules: When using 2 conductors use equal cross-sections.
Rating data for approved types
Auxiliary contacts
Pilot Duty
AC operated D300
DC operated R300
General Use
AC V 240 V/1,5 A
600 V/0,6 A
Short Circuit Current Rating SCCR
Basic Rating
Notes CB for max. 480 V
SCCR kA 5
max. Fuse A 3
max. CB A 15
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 1
Heat dissipation per pole, current-dependent P
vid
W 1.6
06/18/2021 Eaton 014376 ED2021 V80.0 EN 3 / 7