Data Sheet

DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 10
Voltage per contact pair in series V 60
DC-21A I
e
A
Rated operational current I
e
A 1
Contacts Quantity 1
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current I
e
A 10
Contacts Quantity 1
48 V
Rated operational current I
e
A 10
Contacts Quantity 2
60 V
Rated operational current I
e
A 10
Contacts Quantity 3
120 V
Rated operational current I
e
A 5
Contacts Quantity 3
240 V
Rated operational current I
e
A 5
Contacts Quantity 5
DC-13, Control switches L/R = 50 ms
Rated operational current I
e
A 10
Voltage per contact pair in series V 32
Control circuit reliability at 24 V DC, 10 mA Fault
probability
H
F
< 10
-5
, < 1 fault in 100000 operations
Terminal capacities
Solid or stranded
mm
2
1 x (1 - 2,5)
2 x (1 - 2,5)
Flexible with ferrules to DIN 46228
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Terminal screw M3.5
Tightening torque for terminal screw Nm 1
Technical safety parameters:
Notes B10
d
values as per EN ISO 13849-1, table C1
Rating data for approved types
Terminal capacity
Terminal screw M3.5
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 20
Heat dissipation per pole, current-dependent P
vid
W 0.6
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
01/09/2020 Eaton 013696 ED2019 V63.0 EN 3 / 4