User's Manual
Table Of Contents
- EkaNet™ Hardware Manual
- Table of Contents
- List of Figures
- 1. Introduction
- 2. ECR-2400 Node Hardware
- 3. Elster A3/Alpha Plus Node Hardware
- 4. RESI-MON Node Hardware
- 5. EkaNet Pulse Node Hardware
- 6. Gateway Hardware
ECR-2400 Node Hardware
EkaNet Hardware Manual 2 - 5 10156-07
Eka Proprietary and Confidential
2.2 Installation and Operation
Install the ECR-2400 node in the ECR-2400 meter as shown in Figure 2.3.
1. Connect the ECR-2400 Meter Board to the Meter Interface Connector on
the ECR-2400 Node.
2. Connect the AC power connector on the ECR-2400 node to the line and
neutral connectors on the base of the ECR-2400 meter.
As soon as the meter is installed and powered on, the ECR-2400 node will
begin operation.
2.2.1 What the Blinking Lights Mean
2.2.1.1 The Green LED
During the initial boot up the green LED may blink unevenly. However after 10
seconds the green LED should begin blinking at a steady rate of 1/2 second on
and 1/2 second off. This is considered the node’s “heartbeat.” If the green light
fails to come on, is a solid green, or flashes at any other rate, the node has
malfunctioned and the node must be replaced.
2.2.1.2 The Red LED
During the initial boot up the red LED may blink unevenly. During system
operation the red LED will be a solid red whenever it is communicating with any
other Eka node. If the red light flashes continuously, the node has malfunctioned
and the node must be replaced.
Figure 2.3 Eka Node Placement within a ECR-2400 Meter
AC Power
Connector
Meter Interface
Connector
LED Status Lights
Front Face Plate
ECR-2400 Meter Board
ECR-2400 Node
Antenna