Network Card User Manual
MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide S 164201670 Rev 1
61
For example, the AC Voltage between Phase A and Neutral is available
in register 4010. To read the AC Voltage in Phase A at Panel #1, set the
Modbus program to Unit ID 2 and register 4010:
IP: <IP address of PDU/RPP>
Unit ID: 2
Starting Register: 4010
Number of Registers: 2
Function Code: 04
To read the AC Voltage in Phase A at Panel #4, set the Modbus program
to Unit ID 5 and register 4010:
IP: <IP address of PDU/RPP>
Unit ID: 5
Starting Register: 4010
Number of Registers: 2
Function Code: 04
Table 5. Panel Summary Registers (FC 04)
Name Register Data Type Bytes
Display Template 1000 UINT 2
Vendor Name 1001 STRING 64
Model Name 1033 STRING 64
Display Name 1065 STRING 64
Serial Number 1123 STRING 64
Device Volts Rating 1202 UINT 4
Number of Phases 1208 UINT 2
Asset ID 1324 STRING 128
Breaker Rating 1453 UINT 2
Breaker Warning 1456 UINT 2
Breaker Overload 1457 UINT 2
Neutral Current Alarm 1459 UINT 2
Enter Admin State 3047 UINT 2
Enter Operating State 3048 UINT 2
Enter Readiness State 3049 UINT 2
Enter Alarm State 3050 UINT 2
Enter Standby State 3051 UINT 2