Network Card User Manual
MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide S 164201670 Rev 1
59
Table 4. PDU/RPP Alarms (FC 02) (continued)
Data TypeRegisterName
System Alarm Active 1186 BOOL
Inverter Rotation 1192 BOOL
Invalid Board ID 1195 BOOL
Output Watts Overload 1197 BOOL
Xformer Over Temp Warning 1210 BOOL
Input THD High A 1212 BOOL
Input THD High B 1213 BOOL
Input THD High C 1214 BOOL
Output THD High A 1215 BOOL
Output THD High B 1216 BOOL
Output THD High C 1217 BOOL
Neutral Overload Warning 1218 BOOL
Neutral Overload 1219 BOOL
Ground Current Warning 1220 BOOL
Ground Current Overload 1221 BOOL
V Input THD Warning A 1222 BOOL
V Input THD Warning B 1223 BOOL
V Input THD Warning C 1224 BOOL
I Input THD Warning A 1225 BOOL
I Input THD Warning B 1226 BOOL
I Input THD Warning C 1227 BOOL
V Output THD Warning A 1228 BOOL
V Output THD Warning B 1229 BOOL
V Output THD Warning C 1230 BOOL
I Output THD Warning A 1231 BOOL
I Output THD Warning B 1232 BOOL
I Output THD Warning C 1233 BOOL
Panel Phase A Loss 1235 BOOL
Panel Phase B Loss 1236 BOOL
Panel Phase C Loss 1237 BOOL