Table 4. PDU/RPP Alarms (FC 02)
Name Register Data Type
AC Input Over Volts 1006 BOOL
AC Input Under Volts 1007 BOOL
Input Frequency Fault 1008 BOOL
AC Output Over Volts 1009 BOOL
AC Output Under Volts 1010 BOOL
AC Output Frequency Fault 1011 BOOL
Remote EPO 1012 BOOL
Building Alarm 4 1016 BOOL
Building Alarm 3 1017 BOOL
Building Alarm 2 1018 BOOL
Building Alarm 1 1019 BOOL
Output Overload 1025 BOOL
System Bus Overload 1050 BOOL
NV Memory Failure 1053 BOOL
Internal Comm Failure 1062 BOOL
Input Phase Rotation 1089 BOOL
Emergency Shutdown 1093 BOOL
Overload A 1139 BOOL
Overload B 1140 BOOL
Overload C 1141 BOOL
Overload High Phase A 1142 BOOL
Overload High Phase B 1143 BOOL
Overload High Phase C 1144 BOOL
Overload Extreme Phase A 1145 BOOL
Overload Extreme Phase B 1146 BOOL
Overload Extreme Phase C 1147 BOOL
Xformer Over Temperature 1164 BOOL
Check Modem 1174 BOOL
Configuration Error 1182 BOOL
System Notice Active 1185 BOOL