Network Card User Manual
MODBUS REGISTERS
EATON Power Xpert
®
Gateway Series 1000 Card User’s Guide S 164201670 Rev 1
55
Table 3. PDU/RPP Registers (FC 04) (continued)
BytesData TypeRegisterName
Number of Phases 1208 UINT 2
Parallel System Flag 1209 UINT 2
Number of Controlled Banks 1210 UINT 2
Device Topology 1211 UINT 2
Asset ID 1324 STRING 128
Number of Panels 1453 UINT 2
Status 3000 UINT 2
Redundant State 3004 UINT 2
Horn Status 3005 UINT 2
Enter Admin State 3047 UINT 2
Enter Operating State 3048 UINT 2
Enter Readiness State 3049 UINT 2
Enter Alarm State 3050 UINT 2
Enter Standby State 3051 UINT 2
ACVinPhaseAB 4028 FLOAT 4
ACVinPhaseBC 4030 FLOAT 4
ACVinPhaseCA 4032 FLOAT 4
ACVinPhaseA 4040 FLOAT 4
ACVinPhaseB 4042 FLOAT 4
ACVinPhaseC 4044 FLOAT 4
AC V out Phase A 4046 FLOAT 4
AC V out Phase B 4048 FLOAT 4
AC V out Phase C 4050 FLOAT 4
ACVratioAin 4154 FLOAT 4
ACVratioBin 4156 FLOAT 4
ACVratioCin 4158 FLOAT 4
AC V ratio A out 4160 FLOAT 4
AC V ratio B out 4162 FLOAT 4