Cut Sheet
0.63"
(15.9mm)
FUSE
Dimensional Data
.720"
(18.29mm)
C
L
.850"
(21.59mm)
.850"
(21.59mm)
2.250"
(57.15mm)
.740"
(18.80mm)
.870"
(22.10mm)
.635"
(16.13mm)
.255"
(6.48mm)
.410"
(10.41mm)
Keyhole Punch
Knockout Hole
Line Lead
Load Lead
Catalog Symbols: GMF, GRF & HLR
Time-Delay
Non-Rejection Style Fuse
GMF GRF
Amperes
⁄Ω•
-6
⁄Ω¢,10
7-10
Volts AC 300 300
Interrupting Rating: 10,000 Amperes
Agency Information:
GMF and GRF Fuse:
UL Listed, Std. 248-14, Guide JDYX, File E19180
CSA Certified, C22.2 No. 248.14, Class 1422-01, File 53787
HLR Fuseholder:
UL Recognized, 12A, 300 Vac, Guide IZLT2, File E14853
CSA Certified, 12A, 300 Vac, Class 6225-01, File 47235
HLR-2A:
UL Recognized, 15A, 300 Vac, Guide IZLT2, File E14853
CSA Certified, 15A, 300 Vac, Class 6225-01, File 47235
Specialty Fuse GMF, GRF
Time-Delay, Non-Rejecting
& HLR
Form No. GMF, GRF & HLR
Page 1 of 2
Data Sheet: 2031
Bussmann
®
5-22-02
SB02233
Electrical Ratings for Type GMF and GRF Fuses and
Non-Rejection Style Carriers
Fuse Carrier Fuse Carrier
GMF-‹Ω¡º HLR GMF-3 HLR
GMF-⁄Ω™ HLR GMF-3¤Ω¡º HLR
GMF-flꭧ HLR GMF-4 HLR
GMF-°Ω¡º HLR GMF-5 HLR
GMF-1 HLR GMF-6⁄Ω¢ HLR
GMF-1⁄Ω¢ HLR GRF-7 HLR
GMF-1flꭧ HLR GRF-8 HLR
GMF-2 HLR GRF-10 HLR
GMF-2⁄Ω™ HLR GMF-10 HLR
GMF-2°Ω¡º HLR
General Information:
• HLR carrier comes with 6∑ of #18 red insulated solid copper
wire attached to the line side.
• Customer inserts a #18 insulated solid copper wire into load
side receptacle.
• Order part number HLR-2A to obtain 6∑ of #18 black insulat-
ed solid copper wire pre-installed in a load side receptacle.
• Order part number HLR-2L to obtain 6∑ of #18 black insulated
solid copper wire packaged loose (un-installed).
• An alternative to the HLR fuseholder is the A fuseholder. The
A fuseholder comes WITHOUT
leads. The customer inserts
#18 insulated solid copper wire into the line side receptacle as
well as into the load side receptacle. It has the same body
dimensions, utilizes the same mounting hole, and takes the
same mounting clips as the HLR. The A fuseholder is UL
Recognized, 10A, 300Vac, Guide IZLT2, File E14853 and CSA
Certified, 10A, 300Vac, Class 6225-01, File 47235.
• Fuse and knob are an integral one-piece unit. There are no
replacement knobs (caps).
• Units can be panel mounted with a separate steel clip. For the
knockout hole (see above), choose #BK/A-104. For the key-
hole punch type hole, choose #6374 for panels .043” to .062”
thick, or #4909 for panels .030” to .042” thick.
• Do not put tension on line (rear) terminal of fuseholder.
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000 Vac, 75-1500 Vdc). Refer to Data Sheet: 8002 or contact Bussmann
Application Engineering at 636-527-1270 for more information.
FUSE AND CARRIER
MOUNTING HOLE
GMF & GRF
HLR